2.2.4.

POWERCELL Load Cell

The POWERCELL load cell connection is rated non-incendive on the cFMus approved Division 2
versions of the IND570xx terminal. The non-incendive field circuit wiring (NIFW) parameters are
listed below for the power lines, the transmit circuit and the receive circuit.
2.3.

Non-sparking Approval

The IND570xx has been approved as a non-sparking device for Division 2 and Zone 2
environments. This permits the equipment to be physically located within a Division 2 or Zone 2
area. Certain scale connections have also been evaluated as non-sparking (nA) for the ATEX and
IECEx approvals. This permits connection of a matching type of load cell in Zone 2 areas when the
load cell also has a non-sparking approval. This includes analog load cells, the IDNet High
Precision bases (using the "T-Brick T4" cell), the PBK9xx platforms (using the MPGI cell), or
POWERCELL load cells. Note that the load cell in the platform must also have a non-sparking
approval and the maximum supply voltage listed on the certificate must not be exceeded by the
IND570xx terminal.
30205321
|
05
|
03/2019
Load Cell Power
NIFW
V
/u
= 13.02 VDC
oc
o
I
/I
= 304 mA
sc
o
C
/C
= 1 µF
a
o
L
/L
= 0.6 mH
a
o
Note that there is no I
or I
max
circuit will only use the amount of current required for normal operation – more current cannot
be "forced" into the receive circuit. In this case, there is no need to compare the I
as part of the NIFW calculations.
Load Cell Power
NIFW
V
/u
= 12.5 VDC
oc
o
I
/I
= 1182 mA
sc
o
C
/C
= 59.4 µF
a
o
L
/L
= 0.2 mH
a
o
NOTE: While the IND570xx with IDNet interface has been given a non-sparking approval, at
this time no METTLER TOLEDO High Precision IDNet bases are approved for use within an area
rated as Division 2 or Zone 2/22 in the United States or Canada.
METTLER TOLEDO IND570xx Division 2 and Zone 22 Installation Manual
LC Transmit (RS-422)
NIFW
V
/u
= 3 VDC
oc
o
I
/I
= 250 mA
sc
o
C
/C
= 4.4 µF
a
o
L
/L
= 0.5 mH
a
o
value listed for the RS-422 receive circuit. This is because the
i
LC Transmit (CANbus)
NIFW
V
/u
= 5.3 VDC
oc
o
I
/I
= 200 mA
sc
o
C
/C
= 1000 µF
a
o
L
/L
= 2.0 mH
a
o
LC Receive (RS-422)
NIFW
V
/u
= -8...+12.5 VDC
max
i
- -
C
= 440 pF
i
L
= 0 mH
i
or I
values
max
i
LC Receive (CANbus)
NIFW
V
/u
= 26.8 VDC
max
i
- -
C
= 0.6 nF
i
L
= 0 mH
i
2-7