Electrical wiring

Connection diagram: heat pump system
A
Main outdoor unit
A1
Secondary outdoor unit
Operation wiring (shielded twisted pair cable or shielded pair
B
cable) 5 V DC non-polar H-LINK (field-supplied)
C
Distribution box (field-supplied)
D
Indoor units
Remote control wire (shielded twisted pair cable or shielded pair
E
cable) (field-supplied)
F
Fuse or CB(field-supplied)
10.5 SETTING OF THE DSW SWITCHES ON PCB1
Location of the DSW switches on PCB1.
PSW5
SEG2
SEG1
DSW1
DSW10
C A U T I O N
Before changing the settings of the DIP switches, the voltage
supply should be disconnected. Otherwise, the new settings will
not be valid.
N O T E
Only the DIP DSW1, DSW2 and DSW4 switches can be set
while the voltage supply is connected.
The symbol "■" indicates the position of the DIP switches. The
figures show the position of the DIP switch once the position
setting has been completed.
64
PMML0294A_rev.2_02-2014.indb 64
TB1
TB2
L1 L2 L3 N
1 2 3 4
CB
F
ELB
ELB
CB
3N
F
400V/50Hz
ELB
ELB
CB
3N
400V/50Hz
F
ELB
ELB
1N
220-240V/50Hz
230V/50Hz
PSW2
DSW2
DSW3
DSW4
DSW5
PSW1
PSW3
DSW6
DSW7
PSW4
RSW1
< PCB1 >
PMML0294A rev.2 - 07/2014
A1
TB1
TB2
L1 L2 L3 N
1 2 3 4
B
J
C
C
D
D
L1 L2 N
L1 L2 N
TB1
TB1
TB2
TB2
1 2 A B
1 2 A B
E
E
G
G
H
G
Remote control
H
Indoor unit system number 0
I
Indoor unit system nubmer 1
J
Transmission wire between A and A1
K
CH unit
CB
Circuit breaker (field-supplied)
ELB
Earth Leakage Breaker (field-supplied)
With the DSW4 switch, the unit starts or stops after
10 to 20 sec. of the switch being enabled.
Record the number of the outdoor unit to tell it apart from oth-
ers during service and maintenance operations in this area:
PSW2
PSW5
PSW1
PSW3
PSW4
DSW1, RSW1: refrigerant cycle number setting
Setting required
Setting before RSW1 supply: 0
Setting before DSW1 supply: 0 (digit of tens)
Set each main outdoor unit number on each
refrigerant cycle (Subs-units setting are not
required)
Outdoor and indoor units belonging to the
same refrigerant cycle: setting the same
cycle number in the outdoor and indoor units
(indoor units: DSW5 and RSW2)
I
PSW buttons on PCB1
PSW1: accept.
PSW2, 3, 4 and 5: for checking.