Herunterladen Inhalt Inhalt Diese Seite drucken

Drain Piping; Electric Wiring - Hitachi RAS-10FSXN1E Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 83

DRAIN PIPING

9 DRAIN PIPING
9.1 CONDENSATION DRAINAGE SYSTEM
When the outdoor unit operates in refrigeration or heating mode,
there is a build-up of condensation of the ambient humidity
which, together with rain water, requires draining.
Select a location for the unit which permits adequate drainage.
If necessary, mount an installation suitable for the drainage of
condensation.
!
D A N G E R
Drainage must not take place in areas frequented by pedestrians.
In low temperatures, the drainage water could freeze and lead
to falls. If it is necessary to install the outdoor unit in an area
frequented by pedestrians, an additional drainage tray should
be fitted.
Do not fit drainage pipes or collection trays in cold climates, as
they could freeze and break.
If a condensation drainage kit is required for the outdoor unit,
use the optional drainage kit DBS-TP10A.
9.1.1 Installation position of the optional drainage kit DBS-TP10A
Installation position (example: RAS-10FSXNHE, lower and side
views).

10 ELECTRIC WIRING

10.1 GENERAL INFORMATION
!
C A U T I O N
Before any work to the electrical wiring or regular inspections, switch
off the mains power supply of the indoor and outdoor units. Wait three
minutes before starting installation or maintenance work.
Make sure that the interior and exterior fans have come to a complete
standstill before starting work on the electrical wiring or regular
inspections.
Protect cables, the drainage pipe, electrical components, etc. from
rodents and insects; otherwise these might damage unprotected
components and this could result in fire.
Do not allow cables to come into contact with the refrigerant pipes,
metal edges, printed circuit boards (PCB) or the electric components
inside the unit; the cables may be damaged and this could result in
fire.
Firmly secure the cables inside the indoor unit with plastic flanges.
27
PMML0392B rev.1 - 07/2016
Base of outdoor unit (All measurements are in mm)
SET FREE RAS-(8-12)FSXN1E
and RAS-(5/6)FSXNHE
A
ø26x2
B
ø26x2
C
ø52
E
D
ø26x2
235x113
Drainage hole. Drain boss position (option).
A
For the optional drainage kit DBS-TP10A
Drainage hole. Drain cap position (option).
B
For optional drainage plug
C
Opening for power wiring feed through
D
Opening for communication wiring feed through
E
Opening for feed through of refrigerant pipes
A
Drain pipe
B
Optional drain plug
Drain kit components
Material/
Model
Description
colour
Drain pipe
PP/black
DBS-
Drain plug
PP/black
TP10A
Rubber plug
CR/black
!
D A N G E R
Use an earth leakage breaker with medium sensitivity, and an
activation speed of 0.1 or less. If this is not fitted, there is a risk
of electric shock and/or fire.
Install an earth leakage breaker, fuse and circuit breaker for
each outdoor unit power line. Not fitting it may cause an electric
shock or fire.
SET FREE RAS-(14-16)FSXN1E
and RAS-(8-12)FSXNHE
A
ø26x2
B
ø26x2
C
ø52
E
D
ø26x2
245x138
C
Drain pipes (field-supplied)
D
Base of unit
Qty
Application
2
Drain pipe connection
2
Drain pipe plug
4
Pipe and plug seal

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis