MAIN SAFETY DEVICES
12 MAIN SAFETY DEVICES
Compressor Protection
The compressor is protected by the following devices and their combinations.
•
High Pressure Switch: This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
Oil Heater: This band type heater protects against oil foaming during cold starting, as it is energized while the compressor is
stopped.
AC Fan Motor Protection
Internal thermostat: Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when the fan
motor winding temperature exceeds the setting.
Safety and control device setting for outdoor units
Model
For compressor
Pressure switch
High
Cut-out
Cut-in
Fuse capacity
3N~ 400V 50Hz
CCP timer
Setting time
For condenser AC fan motor
Internal thermostat
DC
Cut-out
AC
Cut-out
Cut-in
For control circuit
Fuse capacity PCB1,5
Fuse capacity PCB3
CCP Timer: Enforced 3 minutes operation and stoppage.
23
PMML0390B REV.0 - 11/2015 - P5416649
RAS-8FSNM
-0.05
MPa
4.15
-0.15
MPa
3.20±0.15
A
40
min.
3
ºC
125±5
ºC
150±5
ºC
150±5
A
5
A
10
RAS-10FSNM
Automatic Reset, Non-Adjustable
(each one for each compressor)
-0.05
4.15
-0.15
3.20±0.15
40
Non-Adjustable
3
Automatic Reset, Non-Adjustable
(each one for each motor)
125±5
150±5
150±5
5
10
RAS-12FSNM
-0.05
4.15
-0.15
3.20 ±0.15
40
3
125±5
150±5
150±5
5
10