Werbung

Betriebsanleitung 364xS
Explosionsgeschützte Geräteausführungen für Nordamerika
gemäß Factory Mutual Standards für Übereinstimmung mit grundlegenden Sicherheitsanforderungen
FM 3600:
Electrical Equipment for use in Hazardous (Classified) Locations, General Requirements.
FM 3610 :
Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III, Division 1, and
Class I, Zone 0 & 1 Hazardous (Classified) Locations.
FM 3611:
Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III Division 1
and 2 Hazardous (Classified) Locations.
FM 3615:
Explosionproof Electrical Equipment.
FM 3810:
Electrical and Electronic Test, Measuring and Process Control Equipment.
NEMA 250: Enclosure for Electrical Equipment (1000 Volts Maximum)
Die 364 Druckmessumformer sind von FM für folgende Class, Divisions und Gas groups, hazardous
classified locations, temperature class und types of protection bescheinigt.
Explosionproof for Class I, Division 1, Groups A, B, C and D, hazardous (classified) locations.
Dust Ignition proof for Class II, III Division 1, Groups E, F and G, hazardous (classified) locations.
Suitable for Class II, III, Division 2, Groups F and G, hazardous (classified) locations.
NonIncendive for Class I, Division 2, Groups A, B, C and D, in accordance with Nonincendive field
wiring requirements for hazardous (classified) locations.
Intrinsically Safe for use in Class I, II and III, Division 1, Groups A, B, C, D, E, F, and G in accordance
with Entity requirements for hazardous (classified) locations.
Temperature class T4 to T6 (dependent on the maximum input current and the maximum ambient
temperature).
Ambient Temperature range -50°C to +85°C (dependent on the maximum input current and the
maximum temperature
class).
Electrical Supply range Minimum 10.5 Volts, Maximum 42 Volts (dependent on the type of protection,
maximum ambient
temperature, maximum temperature class and communication protocol).
Type 4X applications Indoors/Outdoors.
Der Druckmessumformer 364, installiert in Explosionproof Class 1 Division 1 Group A, B, C and D
hazardous (classified) location benötigt kein conduit sealing gemäß
Für einwandfreie Installation des Druckmessumformers 364 das zugehörige control drawing beachten.
Alle angeschlossenen Geräte müssen von FM bescheinigt sein.
Hinweis
FM 3615 sect 4.3 / NEC 501.15.
69
Sicherheit